NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
122
11/04 MN01219002Z-EN
Status[2] Bit 1 Trip I
2
t (if I
2
t option selected):
overload variable short-time delayed
Trip I
mv
(if I
2
t option not selected):
overload constant short-time
delayed
Status[3]
Bit 2 Trip I
r
: overload variable long-time
delayed
Status[4] Bit 3 Trip I
dn
: fault current constant short-
time delayed
Status[5]
Bit 4 Trip Select: time limit with H-
selectivity exceeded (not yet
supported)
Status[6] Bit 5 Trip Com: trip has been initiated via
PROFIBUS-DP
Status[7] Bit 6 Trip Temp: trip due to device
overtemperature (NZM)
Status[8]
Bit 7 Trip Error: trip due to device fault
(NZM)
Octet 22
2)
Alarm conditions
Status[9] Bit 0 Load rejection prewarning
Status[10] Bit 1 Overload range 1
Status[11] Bit 2 Overload range 2
Status[12] Bit 3 Motor protection (only significant
with -ME types, otherwise constant
ā€œ0ā€): the circuit-breaker has
detected an overload case and
demands that the DMI switch off the
motor. If the overload continues, the
circuit-breaker will trip.
Status[13]
Bit 4 Unbalance
Bit 5 Not used
Variable access
(example)
Data position Meaning