NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
134
11/04 MN01219002Z-EN
Circuit-breaker Parameters used object
This object contains the parameters currently used by the
circuit-breaker.
This object is a read only object. It can be accessed by class 1
and/or a class 2 DPV1 master.
Intended usage
Use this object in order to get informed about the
parameters currently in use
Limitation value and delay time of the overload release,
Limitation value and delay time of the short-time delayed
short-circuit release,
Limitation value of the non-delayed short-circuit release,
Limitation value and delay time of the residual-current
protection module,
Characteristic curve used for the short-circuit protection
(I
2
t).
Addressing and length of the object
Please use the following information for addressing of the
object:
API is equal to 0 (only required for class 2 DPV1 master),
Slot number is equal to 0,
The index is equal to 12.
The length of the data to be read is 9 Octets. Please ensure
that you do not enter smaller lengths when calling the Read
service as otherwise you will receive a fault indication.
h
The parameters available depend on the type of electronic
control unit used.