EasyManua.ls Logo

Eaton NZM3 - Page 199

Eaton NZM3
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
194
11/04 MN01219002Z-EN
Ambient mechanical conditions
Electromagnetic compatibility (EMC)
Pollution degree 2
Degree of protection EN 50178
IEC 60529 VBG4
IP20
Oscillations IEC 60068-2-6 10 to 57 Hz (constant
amplitude 0.15 mm)
57 to 150 Hz (constant
acceleration 2 g)
Shocks
IEC 60068-2-27 18 shocks (semi-sinusoidal
15 g/11 ms)
Drop
IEC 60068-2-31 Drop height 50 mm
Free fall, packaged IEC 60068-2-32 1 m
Electrostatic discharge IEC/EN 61000-4-2, degree of
severity 3
8 kV air discharge,
6 kV contact discharge
Electromagnetic fields
IEC/EN 61000-4-3 Field strength 10 V/m
Radio interference suppression EN 55011, EN 55022 Limit class A
Burst IEC/EN 61000-4-4, degree of
severity 3
2 kV supply lines,
1 kV signal lines
High-energy pulses (surge)
DMI IEC/EN 61000-4-5, degree of
severity 2
0.5 kV power cable
symmetrical
Line-conducted interference IEC/EN 61000-4-6 10 V
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com