EasyManua.ls Logo

Eaton NZM3 - Page 30

Eaton NZM3
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering and installation
25
11/04 MN01219002Z-EN
X Fasten the cable also to one of the straps provided on the
circuit-breaker.
X Connect both of the auxiliary switches to the NZM:
Input 4 of the DMI is connected to the auxiliary switch
for trip release recognition (tripped = L, not tripped =
H),
Input 5 of the DMI is connected to the auxiliary switch
for ON/OFF detection (ON = H, OFF = L).
The circuit-breaker and DMI will exchange data within 5 s of
connecting the cable at both ends. All the available
parameters and data can then be interrogated as required.
h
For further information refer to the relevant
documentation for the individual NZM types as this varies
according to the type and model concerned.