NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
80
11/04 MN01219002Z-EN
Bus terminator
The bus must be terminated with a bus terminator resistor at
the first and last physical slaves in a bus segment.
The PROFIBUS-DP data plug from Eaton enables switch on
and off of the bus terminator on the connector.
Potential isolation
The following potential isolation applies:
Figure 17: Potential isolation between the supply voltage and
outputs
a Safe isolation EASY-LINK 240 V AC
b Simple isolation PROFIBUS-DP
c Supply voltage 24 V DC
Baud rates
The NZM-XDMI-DPV1 automatically recognises the baud
rate. The following baud rates are supported:
9.6 kBit/s,
19.2 kBit/s,
93.75 kBit/s,
187.5 kBit/s,
500 kBit/s,
1.5 MBit/s,
3 MBit/s,
6 MBit/s,
12 MBit/s.