Modbus Register Maps
2758 - 2758 10073 - 10073 Digital Output States UINT16 bit-mapped -------- ----4321 One bit for each output.
Bit 4 is for output #4,
and bit 1 is for output
#1. If a bit is set the
output is closed, other-
wise it is opened.
1
2759 - 2759 10074 - 10074 Pulse Output Test Select UINT16 bit-mapped -------- ----4321 Writing 1 in bit N sets
Pulse Output N+1 in test
mode. Writing 0 oth-
erwise, reestablished
the output in normal
operation (only while in
privileged session).
When Reading this
reports which Pulse
Output is under test
according to the bits set
or cleared (1=under test,
0=normal).
1
275A - 275A 10075 - 10075 Pulse Output Test Power UINT16 bit-mapped ddvvvvvv vvvvvvvv This register is Write-
able in privileged
session only.
Simulates constant
Power for the Pulse Out-
put under test. Format is
same as Kt settings for
Pulse Output.
"V" is raw value in Wh/
pulse from 0 to 9999.
"dd"=decimal point
position: 00=0.XXXX,
01=X.XXX, 10=XX.XX,
11= X.XXX.
1
275B - 275E 10076 - 10079 Reserved
Reserved 4
275F - 275F 10080 - 10080 Input 1 Accumulator, Scaled UINT16 0 to 9999 resolution is 1, 10, 100,
1000, 10000, or 100000
counts
Disabled accumulators
always read 0.
1
2760 - 2760 10081 - 10081 Input 2 Accumulator, Scaled UINT16 0 to 9999 1
2761 - 2761 10082 - 10082 Input 3 Accumulator, Scaled UINT16 0 to 9999 1
2762 - 2762 10083 - 10083 Input 4 Accumulator, Scaled UINT16 0 to 9999 1
2763 - 2763 10084 - 10084 Output 1 Accumulator, Scaled UINT16 0 to 9999 1
2764 - 2764 10085 - 10085 Output 2 Accumulator, Scaled UINT16 0 to 9999 1
2765 - 2765 10086 - 10086 Output 3 Accumulator, Scaled UINT16 0 to 9999 1
2766 - 2766 10087 - 10087 Output 4 Accumulator, Scaled UINT16 0 to 9999 1
2767 - 2790 10088 - 10129 Reserved
Reserved 42
Block Size: 58
Data and Control Block--Analog Out 0-1mA / Analog Out 4-20mA (Note 15) read-only