PREPARED BY
EricSNims
DATE
04/29/13
APPROVED BY DATE
04/29/13
VERSION
7.9
NEG-ALT NUMBER
PX900719Y201-C001
REVISION DWG SIZE
A
Eaton Corporation
JOB NAME
Banner Health Centers
DESIGNATION
Panel UPS
TYPE
PRL1a
DRAWING TYPE
Final
G.O.
SPX0361126
ITEM
026I
SHEET
1 OF 1
12
34
56
78
910
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
BAB1020
BAB1020
BAB1020
BAB1020
BAB1020
BAB2020
BAB1020
BAB1020
BAB1020
BAB1020
BAB1020
BAB1020
PROV
PROV
PROV
PROV
PROV
PROV
PROV
PROV
PROV
PROV
PROV
PROV
PROV
PROV PROV
PROV PROV
Main Lugs Only
100A
Blank Cover
4 inches
General Information
(Section 1 of 1)
Service Voltage:
208Y/120V 3Ph 4W
Enclosure:
Type 1
Bus Rating & Type:
100A Copper
Neutral Rating:
100A
Ground Bar:
Std. Bolted Copper, Cu cable only
S.C. Rating:
10k A.I.C.Fully Rated
Main Device Type:
Main Lugs Only - Top Cable Entry
Main Terminals:
Mechanical - (1) #14-1/0 (Cu/Al)
Neutral Terminals:
Mechanical - (1) #14-1/0 (Cu/Al)
Box Catalog No.:
EZB2036R
Trim:
EZ Trim, Door in Door, Concealed Hardware (EZT2036S)
Surface Mounted
Box Dimensions:
36." [914.4mm]H x 20" [508.0mm]W x 5.75" [146.0mm]D
Min. Gutter Size:
Top = 5.5" [139.7mm] Bottom = 5.5" [139.7mm]
Left = 6.0" [152.4mm] Right = 6.0" [152.4mm]
Panel ID Nameplate: (1) Panel UPS
(2) 208Y/120V 3Ph 4W
(3) 100A MLO
Type:
Plastic, screw-on
Color:
Red with White Letters
NEC Lighting & Appliance, UL CTL ***Non-Interchangeable Main Device***
Branch Devices
Qty Poles Trip Frame Amps KAIC
11 1 20 BAB 100 10
1 2 20 BAB 100 10
17 1 PROV
Copper Neutral
Trim Lock:Standard Lock & Key (Keyed WEM2)
Circuit Directory:Metal Frame with Plastic Cover
Permanent Circuit Numbers
Do not connect breakers with combined ampere ratings that exceed 140 amperes
on any individual branch bus connector.
Device Modifications:
Ref # Description
Notes: