EasyManua.ls Logo

Eaton Power Xpert 9395P-900 Series - Page 107

Eaton Power Xpert 9395P-900 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS System Installation
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 4-29
Table 4-1. TB1, TB2, and TB3 Interface Connections
Terminal TB1 Name Description
1 REPO NC
Input: Normally-closed dry contact used to activate UPS EPO from a remote switch.
2 REPO Return
3 REPO NO
Input: Normally-open dry contact used to activate UPS EPO from a remote switch.
4 REPO Return
5 Battery Aux
Input: Normally-open contact used to indicate when UPS battery breaker is open or closed
6 Battery Aux Common
7 48 Vdc Battery Shunt Trip +
Output: Contacts used to open battery breaker or disconnect.
8 48 Vdc Battery Shunt Trip
9 Output Contactor K3 NC Aux
Output: Normally-closed contact opens when output contactor closes.
10
Output Contactor K3 NC Aux
Common
Terminal TB2 Name Description
1 Pull Chain
Output: Backup control for parallel operation.
2 Pull Chain Common
3 Alarm Relay NC
Output: General purpose normally-closed (NC) relay contact.
4 Alarm Relay Common
5 Alarm Relay NO
Output: General purpose normally-open (NO) relay contact.
6 Alarm Relay Common
7 Not Used
8 Not Used
9 Not Used
10 Not Used
Terminal TB3 Name Description
1 Building Alarm 1
Input: Programmable UPS alarm, activated by a remote dry contact closure.
2 Building Alarm 1 Return
3 Building Alarm 2
Input: Programmable UPS alarm, activated by a remote dry contact closure.
4 Building Alarm 2 Return
5
Building Alarm 3 Default:
Charger Off
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for charger off.
6 Building Alarm 3 Return
7
Building Alarm 4 Default: On
Generator
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for on generator.
8 Building Alarm 4 Return
9
Building Alarm 5 Default:
Maintenance Bypass
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for maintenance bypass.
10 Building Alarm 5 Return
NOTE “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact.

Table of Contents

Related product manuals