UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 3-3
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in Table 3-2. Dimensions are in
millimeters (inches).
The basic environmental requirements for operation of the UPS are:
l
For all ratings except 900 kW, 600 kW: 0 to 40°C (32–104°F) at elevations up to 1000m without derating
l
For 900 kW: 0–35°C (32–95°F) at elevations up to 1000m without derating
l
Recommended Operating Range: 20–25°C (68–77°F)
l
Maximum Relative Humidity: 95%, non-condensing (see section 3.2.1)
Table 3-1. UPS Cabinet Maximum Weights
Model Section
Maximum Weight
kg (lb)
Shipping Installed
Eaton 9395P-900/900*
Eaton 9395P-900/900
Eaton 9395P-900/825
Eaton 9395P-900/750
Eaton 9395P-900/675
ISBM (CSS) 808 (1782) 764 (1684)
3XUPM 1658 (3656) 1611 (3552
FI-UPM 496 (1094) 475 (1047)
Eaton 9395P-900/600*
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
ISBM (CSS) 808 (1782) 764 (1684)
2XUPM 1152 (2541) 1125 (2418)
NOTE CSS = Continuous Static Switch
NOTE CSS = Table 3-3 describes power ratings of each model.
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet 457.2 mm (18”) minimum clearance for ventilation
From Front of Cabinet 1067mm (42") working space
From Back of Cabinet None Required
From Right Side of Cabinet None Required
From Left Side of Cabinet None Required
NOTE Eaton battery cabinets are located in the same room as the UPS, the battery cabinet
environmental requirements supersede the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life
and performance, and will reduce or void the battery warranty. Refer to Eaton's
Terms and Conditions of Sale with Battery Replacement Coverage and the Battery
Replacement Price Book for more information. These documents can be found at
www.eaton.com/powerquality or contact an Eaton service representative for
information on how to obtain copies.