UPS Installation Plan and Unpacking
3-28 Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual
P-164000501—Rev 09 www.eaton.com/powerquality
Table 3-17. UPS Intercabinet Power Cable Terminations for the Three/Four UPM Models
Terminal Function Terminal Function Bus Landings
Tightening Torque
Nm (lb ft)
Stud
AC Input to UPM Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4 – Four UPM Model)
Phase A 4 – stud mounting 14.2 (10.4) M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4 – Four UPM Model)
Phase B 4 – stud mounting 14.2 (10.4) M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 – Four UPM Model)
Phase C 4 – stud mounting 14.2 (10.4) M8
AC Output from UPM
Section
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
E9A (UPM 4)
Phase A 4 – stud mounting 14.2 (10.4) M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
E10A (UPM 4)
Phase B 4 – stud mounting 14.2 (10.4) M8
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
E11A (UPM 4)
Phase C 4 – stud mounting 14.2 (10.4) M8
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
E12A (UPM 4)
Neutral 4 – stud mounting 14.2 (10.4) M8
DC Input to UPM Section
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
3E4A (UPM 4)
Positive
6 – stud mounting
(2 per UPM)
14.2 (10.4) M8
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
3E5A (UPM 4)
Negative
6 – stud mounting
(2 per UPM)
14.2 (10.4) M8
Table 3-18. Supplied Intercabinet Wiring Terminal Hardware Kit
Part Size Quantity Terminals Used On Eaton Part Number
Flat Washer M8 36
UPM AC Input, UPM Battery Input, UPM AC
Output
180500036-080
Conical Washer M8 36
UPM AC Input, UPM Battery Input, UPM AC
Output
180500037-080
Nut M8 36
UPM AC Input, UPM Battery Input, UPM AC
Output
180200001-05