UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 3-41
ATTENTION!
Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et
communiquer avec un représentant du service Eaton immédiatement.
2. Use a forklift or pallet jack to move the packaged cabinets to the installation site, or as close as possible,
before unpacking. If possible, move the cabinets using the pallet. Insert the forklift or pallet jack forks from
the right side of the pallet (facing the cabinet), between the supports on the bottom of the pallet (see
Figure 3-13 to Figure 3-16 for the UPS cabinet center of gravity measurements). If the cabinets must be
moved using the cabinet front or rear fork lift slots, see the caution statement at the beginning of this
procedure.
CAUTION
Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over.
ATTENTION!
Ne pas incliner les armoires d’onduleur à plus de 10 degrés de la verticale puisqu’elles pourraient
se renverser.
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for
removing the cabinet from the pallet.
4. Remove the protective covering from the cabinets.
5. Remove the packing material, and discard or recycle in a responsible manner.
6. Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact an Eaton service representative immediately to
determine the extent of the damage and its impact on further installation.
NOTE For the following step, verify that the forklift or pallet jack is rated to handle the
weight of the cabinet (see Table 3-1 for cabinet weight).
NOTE The ISBM and UPM sections are shipped with debris shields covering the
ventilation grills on top of the sections (see Figure 4-15). Do not remove the debris
shields until installation is complete.
NOTE While waiting for installation, protect the unpacked cabinets from moisture, dust,
and other harmful contaminants. Failure to store and protect the UPS properly may
void your warranty.