P-164000476 9395P 500kVA / 600 kVA 3
Revision 002 Userās and Installation Guide
1.1.4 Advanced Battery Management
A three-stage charging system increases battery service life by optimizing recharge time, and protects
batteries from damage due to high current charging and inverter ripple currents. Charging at high
currents can overheat and damage batteries.
1.1.5 Power Management Software
Eaton LanSafeĀ® Power Management Software is bundled as part of the Software Suite CD shipped
with the UPS. See Chapter 8: āCommunicationā for additional information.
1.2 Options and accessories
Contact an Eaton sales representative for information about the following options.
1.2.1 Integrated battery cabinet
Battery backup protection can be enhanced by equipping the UPS system with up to four Eaton 9395P
battery cabinets containing sealed lead-acid, maintenance-free batteries. The battery cabinet is
available in one size, with a 240-cell configuration. The cabinets are designed for line-up-and-match
installation, but may be installed separate from the UPS cabinet.
1.2.2 Field Installed UPM
A Field Installed UPM (FI-UPM) provides N+1 redundancy for the UPS system. The FI-UPM may be
installed at any time in the future when power needs change. The module cabinet is installed on the
left side of the UPS and is wired directly to the UPS. No input or output wiring changes are needed for
redundancy. Operation remains the same as for the original UPS.
1.2.3 Sync Control
An optional Eaton 9395P Sync Control maintains the critical load outputs of two separate single
module Eaton 9395P UPS systems in synchronization. This option facilitates the uninterrupted transfer
of the load from one load bus to another by means of a transfer switch. The Sync Control is housed in
a wall-mounted panel that can be located between the UPS units for easy wiring.
1.2.4 Single-feed kit
An optional kit is available for converting the dual-feed rectifier and bypass inputs to a single-feed
configuration. The kit consists of jumpers and bus bar extenders for each phase, and the hardware
required for installation.
1.2.5 Separate rectifier input (factory-installed option)
The Eaton 9395P 500 kVA / 600 kVA UPS can be supplied with separate rectifier inputs for each UPM.
Separate inputs provide increased flexibility and reliability by allowing multiple input sources to supply
the UPS. Input circuit breaker CB1 is not installed with this configuration. AC input control to the UPS
and each UPM rectifier is to be provided by the customer.