P-164000476 9395P 500kVA / 600 kVA 13
Revision 002 Userās and Installation Guide
Table 3-3: Air conditioning or ventilation requirements during full load operation
Ventilation required for cooling air exhaust: approximately 920 liter/sec/250-300kVA unit, + 280 liter/sec
(ISBM).
Figure 3-1. UPS cabinet dimensions (front view)
Rating/kVA
Heat rejection
kW
Heat rejection
BTU / h x 1000
500 kVA 19.8 67.6
600 kVA 25.5 87.0