P-164000476 9395P 500kVA / 600 kVA 20
Revision 002 Userās and Installation Guide
Figure 5-7. Warning label
Terminals E1 through E12 are 2-hole bus bar mountings. See Table 5-6 for power cable terminations
and Table 5-7 for recommended installation parts not supplied by Eaton Corporation. Figure 4-5 on
page 37 through Figure 4-9 on page 42 show the location of the power cable terminals inside the UPS.
Table 5-6:
UPS cabinet power cable terminations for the 9395P 500 kVA / 600 kVA
Bypass terminations are not applicable to IOM configurations.
Terminal function Terminal Function Bus landing Tightening torque Nm Bolt size
AC input to UPS rectifier E1 Phase L1 4-2 bolt mounting 76 M12
E2 Phase L2 4-2 bolt mounting 76 M12
E3 Phase L3 4-2 bolt mounting 76 M12
AC input to bypass E6 Phase L1 4-2 bolt mounting 76 M12
E7 Phase L2 4-2 bolt mounting 76 M12
E8 Phase L3 4-2 bolt mounting 76 M12
AC output to critical load E9 Phase L1 4-2 bolt mounting 76 M12
E10 Phase L2 4-2 bolt mounting 76 M12
E11 Phase L3 4-2 bolt mounting 76 M12
DC input from battery to UPS E4 Battery (+) 4-2 bolt mounting 76 M12
E5 Battery (-) 4-2 bolt mounting 76 M12
Input and output neutral E12 Neutral 8-2 bolt mounting 22 M10
Customer ground Ground Ground 7-1 bolt mounting 22 M10