P-164000476 9395P 500kVA / 600 kVA 52
Revision 002 User’s and Installation Guide
Figure 4-15. Normally-closed remote EPO switch wiring
NOTE
Remote EPO switch rating is 24 Vdc, 1 A minimum.
Remote EPO normally-open and normally-closed return terminals are separated on the terminal
board, but are connected together.
Figure 4-16. Normally closed and normally open remote EPO switch wiring
NOTE
Remote EPO switch rating is 24 Vdc, 1 A minimum.
Remote EPO normally-open and normally-closed return terminals are separated on the terminal
board, but are connected together.