P-164000476 9395P 500kVA / 600 kVA 60
Revision 002 Userās and Installation Guide
Always confirm contact operation prior to wiring.
Table 5-4: Pull-Chain wiring terminations with MOBs
From To Function
UPS 1 CAN Bridge Card J3-1 (Alarm) MOB 1 Aux 1 NC MOB Open Alarm
UPS 1 CAN Bridge Card J3-2 (Alarm
Return)
MOB 1 Aux 1 Com
UPS 1 TB2-1 (Pull Chain) MOB 1 Aux 2 NO Pull Chain
UPS 1 TB2-2 (Pull Chain Common) UPS 2 TB2-2 (Pull Chain Common) Pull Chain Common
UPS 2 CAN Bridge Card J3-1 (Alarm) MOB 2 Aux 1 NC MOB Open Alarm
UPS 2 CAN Bridge Card J3-2 (Alarm
Return)
MOB 2 Aux 1 Com
UPS 2 TB2-1 (Pull Chain) MOB 2 Aux 2 NO Pull Chain
UPS 2 TB2-2 (Pull Chain Common) UPS 3 TB2-2 (Pull Chain Common) Pull Chain Common
UPS 3 CAN Bridge Card J3-1 (Alarm) MOB 3 Aux 1 NC MOB Open Alarm
UPS 3 CAN Bridge Card J3-2 (Alarm
Return)
MOB 3 Aux 1 Com
UPS 3 TB2-1 (Pull Chain) MOB 3 Aux 2 NO Pull Chain
UPS 3 TB2-2 (Pull Chain Common) UPS 4 TB2-2 (Pull Chain Common) Pull Chain Common
UPS 4 CAN Bridge Card J3-1 (Alarm) MOB 4 Aux 1 NC MOB Open Alarm
UPS 4 CAN Bridge Card J3-2 (Alarm
Return)
MOB 4 Aux 1 Com
UPS 4 TB2-1 (Pull Chain) MOB 4 Aux 2 NO Pull Chain
MOB 1 Aux 2 COM MOB 2 Aux 2 Com Pull Chain MOB Common
MOB 2 Aux 2 COM MOB 3 Aux 2 Com
MOB 3 Aux 2 COM MOB 4 Aux 2 Com