EasyManua.ls Logo

Eaton Power Xpert 9395P - Figure 49. Powerware Hot Sync CAN Bridge Card Connections

Eaton Power Xpert 9395P
239 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 93
Figure 49. Powerware Hot Sync CAN Bridge Card Connections
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Alarm
J3
Connections for Bypass Status
Table 23. Powerware Hot Sync CAN Bridge Card Interface Connections
J3 Terminal Name Description
1
Alarm
Programmable UPS alarm. Activated by a remote dry contact closure.
2 Alarm Return
3
Alarm Relay NC Normally closed contact opens when UPS is on bypass.
4
Alarm Relay Com Bypass contact return.
5
Alarm Relay NO Normally open contact closes when UPS is on bypass.
6
TX
RMP II, RIM II, and SCM II connections.
7
TX
8
CAN L
CAN Input for parallel operation.
9
Can H
10
Shield
Installing Options and Accessories

Table of Contents

Other manuals for Eaton Power Xpert 9395P