Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 169
The BYPASS status indicator is illuminated. The Bypass status indicates ON. The UPM status indicates
READY. The power module remains on.
Power is present inside the UPS cabinet.
77..44..1188 TTrraannssffeerr ffrroomm BByyppaassss ttoo OOnnlliinnee MMooddee
To transfer the critical load to Online mode:
1. If not already closed, close the battery breaker.
2. On any UPS, press the CONTROLS pushbutton on the main menu bar. The System Status screen is
displayed.
3. On the System Status screen, select the UPS command.
4. Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
5. On the UPS Control Command screen, select GO TO ONLINE.
6. Press the SELECT pushbutton on the UPS Command menu bar.
All of the UPSs transfer to Online mode. If the power module is not available, the system remains on
bypass and an alarm sounds.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
ONLINE.
77..44..1199 TTrraannssffeerr ffrroomm OOnnlliinnee ttoo BByyppaassss MMooddee aanndd SShhuutt DDoowwnn UUPPMMss
To transfer the critical load to Bypass mode and shut down all UPMs:
1. Transfer the critical load to bypass by performing the procedure in paragraph
7.4.17 Transfer from Online to Bypass Mode.
2. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
3. If UPM 4 (FI-UPM) is installed, proceed to Step 4; otherwise, proceed to Step 8.
4. On the System Status screen, select the UPM command. The UPS Control Command screen is displayed.
5. On the UPS Control Command screen, select the UPM 1 command.
6. Press the CONTROLS pushbutton on the UPS Control Command menu bar. The UPM 1 Control
Command screen is displayed.
7. Proceed to Step 10.
8. On the System Status screen, select the UPM command.
9. Press the CONTROLS pushbutton on the System Status Command menu bar. The UPM 1 Control
Command screen is displayed.
10. On the UPM 1 Control Command screen, select UPM OFF.
11. Press the SELECT pushbutton on the UPM 1 Command menu bar. The UPM status indicates READY. The
input, output, and battery contactors open, and the power module remains on.
12. To turn off the power module, press the CONTROLS pushbutton on the UPS Control Command menu bar.
The UPM 1 Control Command screen is displayed.
13. On the UPM 1 Control Command screen, select UPM OFF.