216 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
1100..22..22 UUPPSS OOuuttppuutt
UPS Output Capacity 100% rated current
Output Voltage Regulation ±1% (10% to 100% load)
Output Voltage Adjustment
(Nominal +/ 3%)
400 Vac nominal, adjustable from 388 Vac to 412 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content 1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current See Table 5 or Table 6 for four UPM models.
See Table 7 or Table 8 for three UPM models.
Output Voltage Balance 3% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement 3° for 100% maximum load imbalance (linear load)
Output Transients ±5% (10% to 100% load)
Frequency Regulation ±0.1 Hz free running
Synchronous to Bypass +10% to -10% ±3%
Frequency Slew Rate 1 Hz per second maximum
Load Compatibility 0.9 pF Leading
0.8 pF Lagging
Overload Capability 110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
NOTE The 110% overload capability in the above table is based on the kVA label rating of the
UPS. The 125% and 150% overloads are based on the non-derated hardware capability
of the UPS.
1100..22..33 UUPPSS EEnnvviirroonnmmeennttaall
Operating Temperature 0 to 40°C (32 to 104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Operating Altitude Maximum 1000m (3000 ft) at 40°C without derating
Storage Temperature –25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self discharge)
Relative Humidity (Operating and Storage)
5% to 95% maximum non-condensing
Acoustical Noise 76 dB at a 1m distance, A weighted
EMI Suppression Meets FCC Regulation 47, Part 15, for class A devices
Electrostatic Discharge (ESD) Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.
Product Specifications