18 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
The basic environmental requirements for operation of the UPS are:
• Ambient Temperature Range: 0–40º C (32–104º F)
• Recommended Operating Range: 20–25º C (68–77º F)
• Maximum Relative Humidity: 95%, non-condensing
If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental
requirements supercede the UPS requirements. Operating temperatures above the recommended range will
result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton’s
Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for
more information. These documents can be found at www.eaton.com/ powerquality or contact an Eaton
service representative to obtain copies.
The UPS ventilation requirements are shown in Table 4.
Table 4. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection BTU/hr
x1000 (kg-cal/hr)
Ventilation Required for
Cooling Air Exhaust
Power Xpert
9395-1100/1000
(CSS)
1000 kVA
400/400
193 (48635)
Approximately 3304 liter/sec (7000 CFM)
480/480
195 (49127)
Power Xpert
9395-1100/1100
(CSS)
1100 kVA
400/400
212 (53499)
480/480
215 (54040)
Power Xpert
9395-1100/650
(CSS)
650 kVA
400/400
125 (31613)
Approximately 2478 liter/sec (5250 CFM)
480/480
127 (31933)
Power Xpert
9395-1100/750
(CSS)
750 kVA
400/400
145 (36476)
480/480
146 (36845)
Power Xpert
9395-1100/825
(CSS)
825 kVA
400/400
159 (40124)
480/480
161 (40530)
Power Xpert
9395-1100/1000
(IOM)
1000 kVA
400/400
193 (48635)
Approximately 3304 liter/sec (7000 CFM)
480/480
195 (49127)
Power Xpert
9395-1100/1100
(IOM)
1100 kVA
400/400
212 (53499)
480/480
215 (54040)
NOTE: CSS = Continuous Static Switch
UPS Installation Plan and Unpacking