Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 29
Table 6. Input/Output Ratings and External Wiring Requirements for the Four UPM Power Xpert 9395-1100/1000, and 9395-
1100/1100 – Separate Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
1000
910
1000
910
1000
1001
1000
1001
Input and Output Voltage Volts 400/400 480/480 400/400 480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
1646 1372 1810 1509
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(4)
500
(5)
500
(5)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
1443
1203 1588 1323
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
350
(4)
500
(5)
500
(5)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
1443
1203 1588 1323
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(6)
500
(5)
500
(6)
500
(6)
DC Input from Each Battery Disconnect to Each UPS
UPM
(1) Positive, (1) Negative
C
Total Amps
551 551 551 551
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
250
(3)
250
(3)
250
(3)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
1443
1203 1588 1323
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(5)
500
(4)
500
(5)
500
(5)
UPS Installation Plan and Unpacking