34 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Table 8. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-1100/650, 9395-
1100/750, and 9395-1100/825 – Separate Battery (Continued)
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
650
592
650
592
750
683
750
683
825
751
825
751
Input and Output Voltage Volts 400/400 480/480 400/400 480/480 400/400 480/480
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
938
782 1083 902 1191 992
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(6)
500
(6)
500
(6)
500
(6)
500
(6)
500
(6)
NOTE: Callout letters A, B, C, and D map to Figure 69.
NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may
interrupt the UPS input neutral during its transition between sources. For the 9395 UPS:
The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS to
operate properly, however it is important to evaluate whether the critical load will function properly as its neutral reference is rapidly
(50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the
return current path and cause a loss of all phase-to-neutral loads.
If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the
transition.
Terminals E1A through E5A and E9A through E12A are stud type terminals. The intercabinet power wiring
connections for this equipment are rated at 90°C. See Table 11 for intercabinet power cable terminations and
Table 12 for supplied intercabinet wiring terminal hardware.
The torque values listed in Table 11 for the M8 studs are the maximum allowable. Tightening further will risk
breaking or twisting the stud.
Figure 23 through Figure 26 show the location of the intercabinet power cable terminals inside the UPS.
Table 9. Bonding Requirements for the Four UPM Power Xpert 9395-1100/1000 and 9395-1100/1100
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
1000
910
1000
910
1100
1001
1100
1001
Input and Output Voltage Volts 400/400 480/480 400/400 480/480
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(1)
4/0
(2)
250
(1)
250
(1)
UPS Installation Plan and Unpacking