Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 35
Table 10. Bonding Requirements for the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
650
592
650
592
750
683
750
683
825
751
825
751
Input and Output Voltage Volts 400/400 480/480 400/400 480/480 400/400 480/480
Neutral Bonding Jumper (Four Wire Output
Only)
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(1)
Table 11. UPS Intercabinet Power Cable Terminations for the Four UPM Power Xpert 9395-1100/1000 and 9395-1100/1100,
and the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825
Terminal Function Terminal Function
Bus Landings
Tightening
Torque Nm
(lb ft)
Stud
AC Input to UPM Section
E1A (UPM 1)
Phase A
3 stud mounting
14.2 (10.4)
M8
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4 Four UPM Model)
E2A (UPM 1)
Phase B
3 stud mounting
14.2 (10.4)
M8
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4 Four UPM Model)
E3A (UPM 1)
Phase C
3 stud mounting
14.2 (10.4)
M8
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 Four UPM Model)
AC Output from UPM Section
E9A (UPM 1)
Phase A
3 stud mounting
14.2 (10.4)
M8
E9A (UPM 2)
E9A (UPM 3)
E10A (UPM 1)
Phase B
3 stud mounting
14.2 (10.4)
M8
E10A (UPM 2)
E10A (UPM 3)
E11A (UPM 1)
Phase C
3 stud mounting
14.2 (10.4)
M8
E11A (UPM 2)
E11A (UPM 3)
E12A (UPM 1)
Neutral
3 stud mounting
14.2 (10.4)
M8
E12A (UPM 2)
E12A (UPM 3)
DC Input to UPM Section
1E4A (UPM 1)
Positive
6 stud mounting (2
per UPM)
14.2 (10.4)
M8
2E4A (UPM 2)
3E4A (UPM 3)
1E5A (UPM 1)
Negative
6 stud mounting (2
per UPM)
14.2 (10.4)
M8
2E5A (UPM 2)
3E5A (UPM 3)
UPS Installation Plan and Unpacking