36 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Table 12. Supplied Intercabinet Wiring Terminal Hardware Kit
Part
Size
Quantity Terminals Used On Eaton Part Number
Flat Washer
M8 36
UPM AC Input, UPM Battery Input, UPM AC Output,
and Neutral
180500036-080
Conical Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC Output,
and Neutral
180500037-080
Nut
M8
36
UPM AC Input, UPM Battery Input, UPM AC Output,
and Neutral
180200001-05
Terminals E1 through E12 are 2-hole busbar mountings for standard NEMA 2-hole barrel lugs.The power wiring
connections for this equipment are rated at 90º C. See Table 13 for power cable terminations, Table 14 for
supplied terminal hardware, and Table 15 for recommended installation parts and tools not supplied by Eaton
Corporation.
Figure 32 through Figure 36 show the location of the power cable terminals inside the UPS.
Table 13. UPS External Power Cable Terminations for the Four UPM Power Xpert 9395-1100/1000 and 9395-1100/1100, and
the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825
Terminal Function Terminal Function
Bus Landings
Tightening Torque
Nm (lb ft)
Bolt
Size
AC Input to UPS Rectifier
E1 Phase A
4 2 bolt mounting
76 (56)
M12
E2
Phase B 4 2 bolt mounting
76 (56)
M12
E3
Phase C 4 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6 Phase A
4 2 bolt mounting
76 (56)
M12
E7
Phase B 4 2 bolt mounting
76 (56)
M12
E8
Phase C 4 2 bolt mounting
76 (56)
M12
AC Output to Critical Load
E9 Phase A
4 2 bolt mounting
76 (56)
M12
E10
Phase B 4 2 bolt mounting
76 (56)
M12
E11
Phase C 8 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
Common Battery
E4
Battery (+)
12 2 bolt mounting (3 UPM)
16 2 bolt mounting (4 UPM)
76 (56)
M12
E5
Battery (-) 12 2 bolt mounting (3 UPM)
16 2 bolt mounting (4 UPM)
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
Separate Battery (UPM 1)
E4
Battery (+) 4 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
Separate Battery (UPM 2)
E4
Battery (+) 4 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
Separate Battery (UPM 3)
E4
Battery (+) 4 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
Separate Battery (UPM 4 FI-
UPM)
E4
Battery (+) 4 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 2 bolt mounting
76 (56)
M12
Input and Output Neutral
E12
Neutral 12 2 bolt mounting