Chapter 5System Configuration and Operation
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 95
Bit 5 0 = no inhibit present
1= C445 control inhibit present
Bit 6 0 = C445 not ready (fault and/or inhibit present)
1= C445 ready for control (No fault or inhibit present)
Bit 7 0 = valve is in not desired end position
1= valve is in desired end position
The following conditions will set the InPos bit in the status
word, signaling the valve has reached the desired end
position.
Normally closed valve
Energize command is active and open feedback detected
De-energize command is active and Closed feedback
detected
Normally open valve
Energize command is active and closed feedback detected
De-energize command is active and open feedback
detected.