Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 225
Ethernet LED Indications
Configuration Using a Web Browser
The Ethernet Card includes an embedded web page that
provides the ability to monitor the status and set the
configuration of the C445 Motor Management Relay System
and the Ethernet Card. The Web Pages have been validated
for use with Internet Explorer. To use the web page open
your Internet Explorer browser and enter the IP address
assigned to the Ethernet Card:
http:// IP Address
The web page provides five levels of authorization as shown
in the chart below:
Note: In addition to the individual levels, a password
exemption setting is provided. This setting specifies a
level that can be accessed without any password
protection. The default value of the password
exemption is Super_User. All capabilities of the web
page are accessible without a password prompt until
the password exemption is changed to a lower level.
User names and passwords are case sensitive, and
limited between 6~16 characters. For security
reasons, it is recommended that the user change the
default passwords and adjust the password
exemption level to be lower than Super_User after
configuration. It is also recommended that these
changes be made within a local subnet.
Refer to System Configuration and Commissioning on
Page 45 for a complete description and procedure on how to
use the password feature for the Web Pages.
Table 88. Ethernet LED Description
LED Description
[1] Ethernet Link status Flashes with Ethernet message activity.
[2] Ethernet Link speed Displays the link speed:
Amber LED on the Ethernet Jack is ON when link speed is 100 mbps
Amber LED on the Ethernet Jack is OFF when link speed is 10 mbps
Table 89. Five Levels Of Authorization
Level
Default
User Name
Default
Password Description
Open <none> <none> Open access, has no password. Allows opening web page to be viewed, but no additional information is available
Read_Only readonly readonly Read_Only access allows parameters to be viewed, but no control or configuration
Control control control Control provides capabilities of Read_Only plus allows motor and discrete outputs to be turned on and off
Config configuration configuration Config provides capabilities of Control plus the ability to set configuration values
Super_User superuser superuser Super_User provides the capabilities of Config plus the ability to change user names and passwords