Appendix C—Optional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 229
Table 93. Assembly Object—Class 0x4 (4)
Class Services
ID Service
0x0E Get_Attribute_Single
0x08 Create
Instance Services
ID Service
0x0E Get_Attribute_Single
0x10 Set_Attribute_Single
0x18 Get_Member
0x19 Set_Member
0x09 Delete
Class Attributes
Sr. No. ID Access Rule Data Type Description Remarks/Default
1 1 (0x1) Get UINT Revision 2
2 2 (0x2) Get UINT Max. Instance 96
3 3 (0x3) Get UINT Number of Instances 09
4 4 (0x4) Get Struct of: Optional Attribute List
UINT Number of Attributes 1
Array of UINT Array of Attributes 04 00
5 6 (0x6) Get USINT Maximum ID Class Attribute 07 00
6 7 (0x7) Get USINT Maximum ID Instance Attribute 04 00
Instance Attributes
Sr. No. ID Access Rule Data Type Description Remarks/Default
1 3 (0x3) Get / Set ARRAY of BYTES Data
24 (0x4)Get Size
Table 94. C445 Assembly Object Instances
Type Instance Description
Output 2 (0x02) Basic Overload
3 (0x03) Basic Motor Starter
5 (0x05) Extended Motor Starter
104 (0x68) Basic Starter Relay
105 (0x69) Basic Output Control
106 (0x6A) Extended Motor Starter 2
123 (0x7B) Basic Starter Relay with Analog and Digital Outputs
124 (0x7C) Basic Starter Relay with Extended Analog and Digital Outputs
125 (0x7D) Basic Output Control with Analog and Digital Outputs
126 (0x7E) Basic Output Control with Extended Analog and Digital Outputs
127 (0x7F) Extended Motor Starter 2 with Basic Analog and Digital Outputs
128 (0x80) Extended Motor Starter 2 with Analog and Digital Outputs
129 (0x81) Extended Motor Starter 2 with Extended Analog and Digital Outputs
130 (0x82) Basic Analog and Digital Outputs
131 (0x83) Extended Analog and Digital Outputs