Appendix COptional Communication Cards
230 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Input 50 (0x32) Basic Overload
51 (0x33) Extended Overload
52 (0x34) Basic Motor Starter
54 (0x36) Extended Motor Starter 2
100 (0x64) Status Current Monitoring
101 (0x65) Status Current Monitoring with Basic Analog and Digital Inputs
102 (0x66) Status Current Monitoring with Analog and Digital Inputs
103 (0x67) Status Current Monitoring with Extended Analog and Digital Inputs
107 (0x6B) Status Current Monitoring
108 (0x6C) Extended Overload with Local IO and Expansion Analog and Digital Inputs
109 (0x6D) Extended Overload with Local IO and Extended Expansion Analog and Digital Inputs
110 (0x6E) Status, Current Voltage, Trip
111 (0x6F) Status Current, Voltage, Trip with Basic Analog and Digital Inputs
112 (0x70) Status Current, Voltage, Trip with Analog and Digital Inputs
113 (0x71) Status Current, Voltage, Trip with Extended Analog and Digital Inputs
114 (0x72) Status Current, Voltage, Trip with Extended Analog and Digital Inputs 2
116 (0x74) Full Monitoring
117 (0x75) Full Monitoring with Basic Analog and Digital Inputs
118 (0x76) Full Monitoring with Analog and Digital Inputs
119 (0x77) Full Monitoring with Extended Analog and Digital Inputs
120 (0x78) Basic Analog and Digital Inputs
121 (0x79) Status and Short Measurements
122 (0x7A) Extended Analog and Digital Inputs
Input-Dynamic 150 (0x96) Dynamic input Assembly
Output Instance 2: Basic Overload
Length = 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved FaultReset Reserved Reserved
Output Instance 3: Basic Motor Starter
Length = 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved FaultReset Reserved Run1
Output Instance 5: Extended Motor Starter
Length = 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved FaultReset Run2 Run1
Table 94. C445 Assembly Object Instances, continued