Appendix COptional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 231
Input Instance 50: Basic Overload
Length = 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Fault/Trip
Input Instance 51: Extended Overload
Length = 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved Reserved Warning Fault/trip
Input Instance 52: Basic Motor Starter
Length = 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved Running 1 Reserved Faulted/Tripped
Input Instance 54: Extended Motor Starter 2
Length = 1 Byte
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Cntr lfrom Net Ready Running 2 Running 1 Warning Faulted/Trip
Input Instance 100 (0x64): Status, Current
Length = 8 Bytes
Byte
Offset
Size
(bytes) Name Description
0 2 Device Status C445_DEVICE_STATUS:
Device Bit Array
Bit 0: Faulted/Tripped
Bit 1: Warning
Bit 2: Output #1
Bit 3: Output #2
Bit 4: Input #1
Bit 5: Input #2
Bit 6: Input #3
Bit 7: Input #4
Bit 8: Running1
Bit 9: Running2
Bit 10: Remote or CtrlFromNet
Bit 11: Output #3
Bit 12: Reserved
Bit 13: Inhibited
Bit 14: Ready
Bit 15: AtRef or Up-To-Speed