Appendix COptional Communication Cards
232 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
2 2 Current I1 MOTOR_I_A_SCALED:
Phase A (L1) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
4 2 Current I2 MOTOR_I_B_SCALED:
Phase B (L2) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
6 2 Current I3 MOTOR_I_C_SCALED:
Phase C (L3) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
Input Instance 101 (0x65): Status Current Monitoring with Basic Analog and Digital Inputs
Length = 20 bytes
Byte
Offset
Size
(bytes) Name Description
0 2 Device Status C445_DEVICE_STATUS:
Device Bit Array
Bit 0: Faulted/Tripped
Bit 1: Warning
Bit 2: Output #1
Bit 3: Output #2
Bit 4: Input #1
Bit 5: Input #2
Bit 6: Input #3
Bit 7: Input #4
Bit 8: Running1
Bit 9: Running2
Bit 10: Remote or CtrlFromNet
Bit 11: Output #3
Bit 12: Reserved
Bit 13: Inhibited
Bit 14: Ready
Bit 15: AtRef or Up-To-Speed
2 2 Current L1 MOTOR_I_A_SCALED:
Phase A (L1) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
4 2 Current L2 MOTOR_I_B_SCALED:
Phase B (L2) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
6 2 Current L3 MOTOR_I_C_SCALED:
Phase C (L3) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
8 2 Digital Inputs Bits 0-7 = Inputs for the first digital input card
Bits 8-15 = Inputs for the second digital input card
10 10 Analog Inputs 5 Input words of data for analog inputs and status word(s)
Input Instance 100 (0x64): Status, Current, continued
Length = 8 Bytes
Byte
Offset
Size
(bytes) Name Description