Appendix COptional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 253
32 4 Trip Reason STATUS_TRIPPED_BITS, continued
0x0004 0000 - overload
0x0008 0000 - stall
0x0010 0000 - phase rotation mismatch
0x0020 0000 - PTC
0x0040 0000 - under voltage restart
0x0080 0000 - peak demand
0x0100 0000 - HRGF pulse detection
36 4 Warning Reason STATUS_WARNING_BITS
Warning/Alarm Indications
0x0000 0001 - under voltage
0x0000 0002 - over voltage
0x0000 0004 - Reserved
0x0000 0008 - ground current warning
0x0000 0010 - current phase loss
0x0000 0020 - current unbalance
0x0000 0040 - instantaneous over current
0x0000 0080 - jam
0x0000 0100 - PF deviation
0x0000 0200 - voltage phase loss
0x0000 0400 - voltage unbalance
0x0000 0800 - freq deviation fast
0x0000 1000 - freq deviation slow
0x0000 2000 - under current
0x0000 4000 - high power
0x0000 8000 - low power
0x0001 0000 - Reserved
0x0002 0000 - exceeds starts limit
0x0004 0000 - overload
0x0008 0000 - stall
0x0010 0000 - phase rotation mismatch
0x0020 0000 - PTC
0x0040 0000 - under voltage restart
0x0080 0000 - peak demand
0x0100 0000 - HRGF pulse detection
40 2 Thermal Pile
Percentage
OVLD_THERMAL_MEM_PERCENT:
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip (%)
42 2 Digital Inputs Bits 0-7 = Inputs for the first digital input card
Bits 8-15 = Inputs for the second digital input card
44 2 Analog Inputs 1 Input word of data for an analog output card status
Input Instance 117 (0x75): Full Monitoring with Basic Analog and Digital Inputs, continued
Length = 46 Bytes
Byte
Offset
Size
(bytes) Name Description