Appendix COptional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 269
Instance Attributes
Sr. No. ID Access Rule Data Type Description
22 111 (0x6F) Get USINT Config Inhibit
Reason
0: No active inhibits
1: Local and Remote motor control sources both point to
Fieldwire
2: Local motor control source is set to User Interface but the
User Interface type does not match
3: One or more enabled protection features requires a
voltage option card in the Measurement Module
4: One or more enabled protection features requires a PTC
(Temperature) option card in the Measurement Module
5: Selected starter profile is incompatible with fieldwire as
local control or fieldwire type
6: Cannot choose fieldwire as the feedback source when the
fieldwire is used as a local / remote source with the selected
starter
7: UI Custom Overlay - Multiple buttons assigned to same
function
8: UI Custom Overlay - Multiple functions assigned to the
same button LED
9: UI Custom Overlay - Multiple functions assigned to the
same status LED
10: Selected starter profile is incompatible with the
connected UI
11: The General Purpose I/O operational mode does not use
fieldwire as a control source
12: Q3 configured for latching relay and shunt trip output
23 112 (0x70) Get/Set USINT Motor Control
Communication
Loss Behavior
0: Stop on comloss event - no fault
1: Ignore comloss and keep present state
2: Send RUN1 command on comloss event
3: Send RUN2 command on comloss event
4: Stop C445 controller and issue comloss fault
4
24 113 (0x71) Get/Set USINT Motor Control
Network Idle
Behavior
0: Stop on idle event
1: Ignore idle and keep present state
2: Send RUN1 command on idle event
3: Send RUN2 command on idle event
0
25 114 (0x72) Get/Set USINT System Services 0: No Active Service
1: Clear fault queue
2: Clear trip snapshot
3: Test trip
4: Re-pair external modules
5: Factory reset
6: Soft reset
7: Reset Fault
8: Proof Test
26 115 (0x73) Get USINT Proof Test
Status
0: Proof Test was never run after a power cycle
1: Proof Test currently running
2: Proof Test passed
3: Proof Test failed
0
27 116 (0x74) Get UINT Base Control
Module Fault
Queue - 1
A list of faults based on most recent. Duplicates are not
allowed. They are sorted by event with the newest at the top
of the queue.
28 117 (0x75) Get UINT Base Control
Module Fault
Queue - 2
A list of faults based on most recent. Duplicates are not
allowed. They are sorted by event with the newest at the top
of the queue.
29 118 (0x76) Get UINT Base Control
Module Fault
Queue – 3
A list of faults based on most recent. Duplicates are not
allowed. They are sorted by event with the newest at the top
of the queue.
Table 98. Control Supervisor Object—Class 0x29 (41), continued