Appendix COptional Communication Cards
300 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
C445 PROFIBUS Bit Mapping Parameters
C445 has option of mapping individual bits in input/output
modules. Below are the bits available for bit mapping.
C445 PROFIBUS Cyclic/Acyclic Writable Parameters
Table 124. Bit Mapping Parameters for Cyclic/Acyclic
Writeable Parameters
Note: For more information about any of the parameters
listed above, refer to System Configuration and
Commissioning on Page 45 or Appendix E.
Table 125. Fieldbus Motor Control Bits
C445 PROFIBUS Cyclic/Acyclic Readable Parameters
Table 126. Bit Mapping Parameters for Cyclic/Acyclic
Readable Parameters
System Services is one of the selections for an output
data word. The following are decimal values that when
sent to the C445 with the System Services word
cause the C445 to perform the designated function:
0: No Active Service
1: Clear Fault Queue
2: Clear Trip Snapshot
3: Test Trip
4: Re-pair external modules
5: Factory Reset
6: Soft Reset
7: Reset Fault
8: Proof Test
BCM Field Output Control Word is one of the
selections for an output data word. The following are
the bits that control the 3 outputs on the Base Control
Module:
Bit 0: Output 1
Bit 1: Output 2
Bit 2: Output 3 (if a Base Control Module with the
latching relay option is being used, this bit is
used to Set this output)
Bit 3: This bit is only used when a BCM with the
latching relay option is used. This bit resets the
latching relay output.
Bit Description Parameter Description
Run 1 Fieldbus Motor Control
Run 2 Fieldbus Motor Control
Reserved Fieldbus Motor Control
Fault Reset Fieldbus Motor Control
Reserved Fieldbus Motor Control
Test Trip Fieldbus Motor Control
Reserved Fieldbus Motor Control
Reserved Fieldbus Motor Control
BCM Field Output control0 BCM Field Output control
BCM Field Output control1 BCM Field Output control
BCM Field Output control2 BCM Field Output control
BCM Field Output control3 BCM Field Output control
Bit Position Bit Description
Bit 0 Run 1
Bit 1 Run 2
Bit 2 Switch to Remote
Bit 3 Fault Reset
Bit 4 Reserved
Bit 5 Test Trip
Bit 6 Reserved
Bit 7 Reserved
Bit Description Parameter Description
Running 1 Status Word
Running 2 Status Word
Remote Enabled Status Word
Faulted Status Word
Warning Status Word
Inhibited Status Word
Ready Status Word
Up to Speed Status Word