SPECIFICATIONS
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide S 164201730 Rev 4
www.eaton.com/powerquality
59
Table 16. Battery Runtimes (in minutes)
+4 EBMs+3 EBMs+2 EBMs+1 EBMUPS Internal BatteriesLoad
PW5130i2500-XL2U (with PW5130N3000-EBM2U)
250 VA/225W 77 300 410 780 1064
625 VA/563W 28 122 207 309 412
1250 VA/1125W 11 55 100 150 206
2153 VA/1938W 6 31 59 90 120
2500 VA/2250W 3 23 42 63 85
PW5130i3000-XL2U / PW5130i3000-XL3U (with PW5130N3000-EBM2U or PW5130N3000-EBM3U depending on UPS
height)
300 VA/210W 80 270 500 705 901
750 VA/525W 39 143 308 370 482
1500 VA/1050W 16 62 117 160 210
2250 VA/1575W 8 35 59 85 105
3000 VA/2100W 5 24 40 59 89
3000 VA/2700W 3 17 32 47 62
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.