EasyManua.ls Logo

Eaton Powerware 9125 - Page 46

Eaton Powerware 9125
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
COMMUNICATION
EATON Powerware
®
9125 (9910-E30) UPS Installation Guide for IBM
®
Applications S 164201696 Rev 1
42
Table 14. Communication Port Pin Assignment
Pin Number Signal Name Function Direction from the UPS
1 Low Batt Low Battery relay contact Out
2 TxD Transmit to external device Out
3 RxD Receive from external device In
4 DTR PnP (Plug and Play) from external device (tied to Pin 6) In
5 GND Signal common (tied to chassis)
6 DSR To external device (tied to Pin 4) Out
7 RTS PnP from external device (default) or On Bypass relay
contact (jumper-selectable)
In / Out
8 AC Fail AC Fail relay contact Out
9 Power Source +V (8 to 24 volts DC power) Out
The On-Bypass Relay Contact. You can enable the On-Bypass relay using
the jumper on the Single-Port Card. The jumper default is disabled. To
enable the On-Bypass relay:
1. Remove the Single-Port Card on the UPS rear panel. Retain the
screws (see Figure 40).
Figure 40. Removing the Single-Port Card
2. Move the J3 jumper to the AS/400
®
position to enable the
On-Bypass relay as shown in Figure 41.

Other manuals for Eaton Powerware 9125

Related product manuals