COMMUNICATION
EATON Powerware
®
9125 (9910-E30) UPS Installation Guide for IBM
®
Applications S 164201696 Rev 1
42
Table 14. Communication Port Pin Assignment
Pin Number Signal Name Function Direction from the UPS
1 Low Batt Low Battery relay contact Out
2 TxD Transmit to external device Out
3 RxD Receive from external device In
4 DTR PnP (Plug and Play) from external device (tied to Pin 6) In
5 GND Signal common (tied to chassis) —
6 DSR To external device (tied to Pin 4) Out
7 RTS PnP from external device (default) or On Bypass relay
contact (jumper-selectable)
In / Out
8 AC Fail AC Fail relay contact Out
9 Power Source +V (8 to 24 volts DC power) Out
The On-Bypass Relay Contact. You can enable the On-Bypass relay using
the jumper on the Single-Port Card. The jumper default is disabled. To
enable the On-Bypass relay:
1. Remove the Single-Port Card on the UPS rear panel. Retain the
screws (see Figure 40).
Figure 40. Removing the Single-Port Card
2. Move the J3 jumper to the AS/400
®
position to enable the
On-Bypass relay as shown in Figure 41.