EasyManua.ls Logo

Eaton Powerware 9390 - Page 192

Eaton Powerware 9390
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
POWER WIRING INSTALLATION NOTES
032406E
164201554---5
13 of 15
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
Installation Information
A-24
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
Table P. INPUT/OUTPUT Ratings for Powerware 9390---120/120 and 9390---160/120 Parallel Systems
Configuration Units Rating 50/60 Hz
BasicUnitRatingat0.9laggingpFload
kVA
kW
120
108
120
108
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
480
480
All
AC Input from UPM
Full Load Current for each Module
(3) Phases, (1) Neutral ---if required, (1) Ground
D
Amps 333/315 144
Minimum Conductor Size for each Module
NumberperPhaseforeachModule
AWG or kcmil
(each)
See Table E through
TableGforwiresize.
1+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 333/315 144
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral ---if required, (1) Ground
G
Amps 333/315 144
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
1/0
(1)
4
(1)
2+0
and
2+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 666/630 288
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral ---if required, (1) Ground
G
Amps 666/630 288
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
3/0
(1)
1/0
(1)
3+0
and
3+1
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 999/945 432
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral ---if required, (1) Ground
G
Amps 999/945 432
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
1/0
(2)
2/0
(1)
4+0
AC Input to Tie Cabinet Bypass (optional)
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 1332/1260 576
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral ---if required, (1) Ground
G
Amps 1332/1260 576
System Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 27)
---
AWG or kcmil
(each)
2/0
(2)
2/0
(1)
NOTE: Callout letters D, F,andG map to drawing 164201554 ---4, sheets 4 of 6, 5 of 6,
and 6 of 6.

Table of Contents

Other manuals for Eaton Powerware 9390

Related product manuals