EasyManua.ls Logo

Eaton PowerXL DA1 - Page 26

Eaton PowerXL DA1
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 CANopen communication settings
4.4 Configuration of the control signal terminals
22 CANopen for DA1, DC1, DE11 09/16 MN040019EN www.eaton.com
Select DIG REF/f-Fix1 DA1 only
Used to select between the digital speed reference value (set with the keypad or with
the UP and DOWN commands) and fixed frequency 1 (f-Fix1) set with P2-01
Low = digital setpoint value
•High = Preset Speed 1
Select f-Fix Bit0
Select f-Fix Bit1
Select f-Fix Bit2
Used to select a fixed frequency with digital commands
Fixed frequencies f-Fix1, …, f-Fix8 are defined with parameters P2-01, …, P2-08.
0 = Low; 1 = High
Select PID REF/AI2 REF
DA1 only
Used to select between setpoint values
Low = Setpoint from the PID controller‘s output
•High = AI2
Select PID REF/f-Fix
DA1 only
Used to select between setpoint values
Low = Setpoint from the PID controller‘s output
High = Fixed frequency
The fixed frequency itself is selected with the
Select f-Fix Bit0, Select f-Fix Bit1, Select f-Fix Bit2 commands.
Select PID REF/f-Fix1
DA1 only
Used to select between setpoint values
Low = Setpoint from the PID controller‘s output
High = f-Fix1 (set with P2-01)
Select Quick-dec
DA1 only
Used to activate a quick stop with the ramp set with P2-25
In order to activate the quick stop, there must be a high signal at both terminals
Select t-dec1/
Select t-dec2
DA1 only
Used to select between deceleration ramp 1 t-dec1 set with P1-04 and deceleration
ramp 2 t-dec2 (P8-11)
Low = Deceleration ramp 1
High = Deceleration ramp 2
START
Used to start/stop the drive
UP Used to increase the speed if a digital setpoint is selected
Used together with the DOWN command.
Abbreviation
Significance
Fixed frequency Bit 2 Bit 1 Bit 0
f-Fix1 (P2-01) 0 0 0
f-Fix2 (P2-02) 0 0 1
f-Fix3 (P2-03) 0 1 0
f-Fix4 (P2-04) 0 1 1
f-Fix5 (P2-05) 1 0 0
f-Fix6 (P2-06) 1 0 1
f-Fix7 (P2-07) 1 1 0
f-Fix8 (P2-08) 1 1 1