3 Installation
3.6 Electrical Installation
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 113
3.6.2.12 IP66, control signal terminals (DA1-…-A6SC)
On DA1 variable frequency drives with an IP66 degree of protection and local
controls (DA1-…A6SC), the control signal terminals will be partially wired.
Figure 83:DA1-…-A6SC (factory connection)
When supplied, the control signal terminals will be connected as follows:
Table 18: Configuration of the control signal terminals
Terminal
Color Function
1 YE (yellow) +24 V to FWD/REV selector switch
2 BU (blue) From selector switch = FWD
3
RD (red) From selector switch = REV
5 GY (gray) +10 V to potentiometer
6 WH (white) From potentiometer = f-Set
7
BK (black) From potentiometer = 0 V
→
For the enable signal for operation, you will also need to install
an insulated wire jumper from terminal 1 to terminal 12 (STO+)
and a link from terminal 13 (STO-) to terminal 9 or 7
( Figure 74, page 104).