3 Installation
3.7 Block diagrams
124 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
3.7.10 DA1-32…-B6SC, DA1-34…-B6SC
Mains voltage U
LN
:
DA1-32…: 3-phase, 200 (-10 %) - 240 (+10 %) V, 50/60 Hz
DA1-34…: 3-phase, 380 (-10 %) - 480 (+10 %) V, 50/60 Hz
Motor voltage U
2
: 3-phase, U
2
= U
LN
, 0 - 50/60 Hz (max. 500 Hz)
Frame size: FS2 and FS3 with IP66 degree of protection
Figure 93:DA1-32…-B6SC, DA134…-B6SC block diagram
Direct enable signal for STO function or relay: Safe Torque Off (STO),
SIL 2 (EN 61800-5-2) as in Figure 85, page 116.
DC+
BR
DC-
3 AC 230/400/460 V
WVU
M
3 ~
EMC
VAR
PES
13
STO-
1
+24 V Out
< 100 mA
2
DI1
3
DI2
4
DI3
10
DI5
(AI2)
12
STO+
5
+10 V Out
< 10 mA
6
AI1
(DI4)
0 V
7
CPUSTO
10 V
0 V
f-Soll
0…+10 V
0…10 V, 0/4… 20 mA
15 16
Error
RUN
17 18 11
14
89
6 A, 250 V AC
5 A, 30 V DC
6 A, 250 V AC
5 A, 30 V DC
0 V
K11
K14
K12
K23
K24
AO2
(DO2)
+24 V
< 10 mA
AO1
(DO1)
PE
RS485
X1
Modbus RTU
CANopen
OP-Bus
FWD
24 V
REV
REV
OFF
FWD
PWR
L1/L
L3
L2/N
DA1-32... 3 AC 200 - 240 V
50/60 Hz
DA1-34... 3 AC 380 - 480 V
50/60 Hz
The STO connection must be made by the user.