4 Operation
4.4 Handling the keypad
136 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
4.4.2 Adjust parameters
Table 20: Modify parameters
4.4.3 Resetting Parameters (RESET)
Table 21: Resetting parameters (RESET)
Commands
Description
Press the OK button and hold it down for two seconds in order to access the parameter interface.
→
The display will show the parameter that was last used.
Use the ▲ and ▼ buttons to select a parameter.
Press the OK button.
The value of the selected parameter can be changed.
Use the ▲ and ▼ buttons to change the parameter’s value.
Press the OK button to confirm the parameter value change.
As soon as the parameter is displayed, the value will have been saved.
Press the OK button and hold it down for two seconds in order to exit the parameter interface (display: "Stop").
Switching between two parameter groups
The parameters are in sequential order. This means that moving forward from the last parameter in a parameter
group will take you directly to the first parameter in the next parameter group and the other way around.
Note: In order to access the extended parameter groups, you will need to enter the corresponding password in
parameter P1-14 (default passwords: level 2 = 101, level 3 = 201).
Press the ▲ and STOP buttons to jump to the first parameter in the next parameter group.
Press the ▼ and STOP buttons to jump to the first parameter in the previous parameter group.
Commands Description
Reset to default settings
++
Press the ▲ and ▼ and STOP buttons and hold them down for two seconds.
→ All parameters will be restored to their default settings.
The display will show
P-dEF.
Resetting after a fault
Press the STOP button to reset a fault message.
The display will show
StoP.