6 Technical Data
6.1 General rating data
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 143
6 Technical Data
6.1 General rating data
Technical data Symbol Unit Value
General
Standards EMC: EN 61800-3:2004+A1-2012
Radio interference: EN 55011: 2010
Safety: EN 61800-5: 2007
Degree of protection: EN 60529: 1992
Note:
DA1-35… devices are not covered by the declaration
of conformity for the EU EMC Directive.
Certifications and manufacturer’s declarations on conformity CE, UL, cUL, c-Tick, UkrSEPRO, Gost-R
Note:
Frame size FS8 is not UL or cUL listed as of this writing.
Production quality RoHS, ISO 9001
Climatic proofing ρ
w
% < 95 %, mean relative humidity (RH),
non-condensing (EN 50178)
Ambient air temperature
Operational
IP20 (NEMA 0) ϑ ?C -10 - +50 (frost-free and condensation-free)
IP55 (NEMA 3) ϑ ?C -10 - +40, with derating of 1.5% per °C above 40 °C on
rated operational current I
e
Note:
Operation within a temperature range of 40 to 50 °C
does not conform to UL listing.
IP66 (NEMA 4X) ϑ °C -10 - +40, with a derating of 2.5% per °C above 40 °C
on rated operational current I
e
Note:
Operation within a temperature range of 40 to 50 °C
does not conform to UL listing.
Storage ϑ °C -40 - +60
MTTF
d
Years 4525
MTBF
(mean time between two failures)
Years 50
PFH
D
1.23 - 09 1/h (0.12 % of SIL)
Electrostatic discharge (ESD, EN 61000-4-2:2009 U kV ±4, contact discharge
±8, air discharge
Fast transient burst (EFT/B, EN 61000-4-4: 2004) U kV ±1, at 5 kHz, control signal terminal
±2, at 5 kHz, motor connection terminals,
Single-phase mains connection terminals
±4, at 5 kHz, three-phase mains connection terminals