6 Technical Data
6.2 Specific rated operational data
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 147
6.2 Specific rated operational data
6.2.1 DA1-12… series
Physical quantity Symbol Unit 4D3 7D0 011
Rated operational current I
e
A 4.3 7.0 10.5
Overload current for 60 s every 600 s i
l
A 6.45 10.5 15.75
Apparent power at rated operation
1)
230 V S kVA 1.71 2.79 4.18
240 V S kVA
1.79 2.91 4.36
Assigned motor power 230 V P kW
0.75 1.5 2.2
230 V P HP 1 2 3
Power side (primary side):
Number of phases single-phase or two-phase
Rated voltage U
LN
V 200 -10% - 240 +10%, 50/60 Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current (phase current) I
LN
A 9 13 19
Minimum braking resistance R
B
Ω 100 50 35
Switching frequency (pulse frequency)
Default settings f
PWM
kHz 16 16 16
Setting range f
PWM
kHz 4 - 32 kHz 4 - 32 4 - 32
Maximum leakage current to earth (PE), without
motor
I
PE
mA 2.49 2.49 2.49
Efficiency η
0.94 0.96 0.95
Heat dissipation at I
e
P
V
W 45.75 63 103.4
Frame size
FS2 FS2 FS2