EasyManua.ls Logo

Eaton PowerXL DA1 - Da1-32

Eaton PowerXL DA1
203 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Technical Data
6.2 Specific rated operational data
148 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
6.2.2 DA1-32… series
Physical quantity Symbol Unit 4D3 7D0 011 018 024 024
Rated operational current I
e
A 4.3 7.0 10.5 18 24 24
Overload current for 60 s every 600 s i
l
A 6.45 10.5 15.75 27 36 36
Apparent power at rated operation 230 V S kVA 1.71 2.79 4.18 7.17 9.56 9.56
240 V S kVA 1.79 2.91 4.36 7.48 9.98 9.98
Assigned Instance Motor Power 230 V P kW 0.75 1.5 2.2 4.0 5.5 5.5
230 V P HP 1 2 3 5 7.5 7.5
Power side (primary side):
Number of phases three-phase
Rated operating voltage U
LN
V 200V -10% - 240V +10%, 50/60Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current (phase current) I
LN
A 6 11 13 21 26 27
Minimum braking resistance R
B
Ω 100 50 35 20 20 20
Switching frequency (pulse frequency)
Default settings f
PWM
kHz 16 16 16 16 16 16
Setting range f
PWM
kHz 4 - 32 4 - 32 4 - 32 4 - 32 4 -16 4 - 16
Maximum leakage current to earth (PE), without motor I
PE
mA 1.73 1.73 1.73 0.93 0.93 1.42
Efficiency η
0.95 0.96 0.96 0.96 0.97 0.97
Heat dissipation at I
e
P
V
W 39.75 61.5 90.2 160 170.5 170.5
Frame size FS2 FS2 FS2 FS3 FS3 FS4