6 Technical Data
6.2 Specific rated operational data
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 151
6.2.3 DA1-34… series
Physical quantity Symbol Unit 2D2 4D1 5D8 9D5 014 018 024
Rated operational current I
e
A 2.2 4.1 5.8 9.5 14 18 24
Overload current for 60 s every 600 s i
l
A 3.3 6.15 8.7 14.25 21 27 36
Apparent power at rated operation 400 V S kVA 1.52 2.84 4.02 6.58 9.7 12.5 16.6
480 V S kVA 1.83 3.41 4.8 7.9 11.6 15 20
Assigned Instance Motor Power 400 V P kW 0.75 1.5 2.2 4.0 5.5 7.5 11
460 V P HP 1 2 3 5 7.5 10 15
Power side (primary side):
Number of phases three-phase
Rated operating voltage U
LN
V 380 V - 10 % - 480 V +10 %, 50/60 Hz
(342 - 528 V ±0 %, 48 - 62 Hz ±0 %)
Input current (phase current) I
LN
A 3.5 6 7.5 12 17 22 28
Minimum braking resistance R
B
Ω 400 200 150 100 75 50 40
Switching frequency (pulse frequency)
Default settings f
PWM
kHz 8 8 8 8 8 8 8
Setting range f
PWM
kHz 4 - 32 4 - 32 4 - 32 4 - 32 4 -24 4 - 24 4 - 16
Maximum leakage current to earth (PE), without
motor
I
PE
mA 4.65 4.65 4.65 4.65 1.55 1.55 1.55
Efficiency η
0.92 0.95 0.95 0.96 0.96 0.97 0.97
Heat dissipation at I
e
P
V
W 63.75 76.5 101.2 136 209 300 297
Frame size FS2 FS2 FS2 FS2 FS3 FS3 FS3