EasyManua.ls Logo

Eaton PowerXL DA1 - 6.3.2 Frame sizes FS4 to FS7 in IP55

Eaton PowerXL DA1
203 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Technical Data
6.2 Specific rated operational data
154 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
6.2.4 DA1-35… series
DA1-35… devices are not covered by the declaration of
conformity.
Additional radio interference suppression filters are required for
compliance.
Physical quantity Symbol Unit 2D1 3D1 4D1 6D5 9D0 012
Rated operational current I
e
A 2.1 3.1 4.1 6.5 9 12
Overload current for 60 s every 600 s at 50 °C i
l
A 3.15 4.65 6.15 9.75 13.5 18
Apparent power at rated operation 500 V S kVA 1.6 2.1 2.4 4.3 6 7.5
600 V S kVA 2 2.5 2.9 5.1 7.3 9
Assigned Instance Motor Power 500 V P kW 0.75 1.5 2.2 4 5.5 7.5
575 V P HP 1 2 3 5 7.5 10
Power side (primary side):
Number of phases three-phase
Rated operating voltage U
LN
V 500V -10% - 600V +10%, 50/60Hz
Input current (phase current) I
LN
A 3.5 4.5 4.5 9 12 15
Minimum braking resistance R
B
Ω 50 50 50 50 50 40
Switching frequency (pulse frequency)
Default settings f
PWM
kHz 8 8 8 8 8 8
Setting range f
PWM
kHz 4 - 24 4 - 24 4 - 24 4 - 24 4 - 24 4 - 24
Maximum leakage current to earth (PE), without motor I
PE
mA
Efficiency η 0.97 0.97 0.97 0.97 0.97 0.97
Heat dissipation at I
e
P
V
W 22.5 45 66 120 165 225
Frame size
FS2 FS2 FS2 FS2 FS2 FS3

Table of Contents

Other manuals for Eaton PowerXL DA1

Related product manuals