1 DA1 device series
1.4 Rated operational data
18 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
1.4.3 Features
Mains supply voltage: 1 AC 230 V
Motor connection voltage: 3 AC 230 V, 50/60 Hz
Type
Rated operational
current
Assigned motor power
(induction motor)
Display (operating
unit)
Local controls
Radio interference
suppression filter
DC link choke
Degree of
protection
Frame size
Brake chopper
I
e
P
1)
(230 V,
50 Hz)
P
2)
(220
-
240 V,
60 Hz)
IP FS B = Yes
A kW HP
DA1-124D3FB-A20C 4.3 0.75 1 LED – ✓ – IP20 FS2 B
DA1-124D3FB-B66C 4.3 0.75 1 OLED – ✓ – IP66 FS2 B
DA1-124D3FB-B6SC
4.3 0.75 1 OLED ✓ ✓ – IP66 FS2 B
DA1-127D0FB-A20C 7 1.5 2 LED – ✓ – IP20 FS2 B
DA1-127D0FB-B66C 7 1.5 2 OLED – ✓ – IP66 FS2 B
DA1-127D0FB-B6SC 7 1.5 2 OLED ✓ ✓ – IP66 FS2 B
DA1-12011FB-A20C 10.5 2.2 3 LED – ✓ – IP20 FS2 B
DA1-12011FB-B66C 10.5 2.2 3 OLED – ✓ – IP66 FS2 B
DA1-12011FB-B6SC 10.5 2.2 3 OLED ✓ ✓ – IP66 FS2 B
1) As per IEC standards
2) Quote from “Power Conversion Equipment - UL 508C, May 3, 2002”.