1 DA1 device series
1.6 Voltage categories
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 27
1.6 Voltage categories
DA1 variable frequency drives are divided into three voltage categories:
200 V: 200 – 240 V ±10 %
DA1-12…, DA1-32
400 V: 380 – 480 V ±10 %
DA1-34
575 V: 500 – 600 V ±10 %
DA1-35
DA1-12
Single-phase mains connection, rated operating voltage 230 V
U
LN
= 1~, 200 - 240 V ±10 %, 50/60 Hz
I
e
= 4.3 - 11 A
Motor: 0.75 - 2.2 kW (230 V, 50 Hz), 1 - 3 HP (230 V, 60 Hz)
Figure 15:DA1-12…FB-…
DA1-32
Three-phase power supply, rated operating voltage 230 V
U
LN
= 3~, 200 - 240 V ±10 %, 50/60 Hz
I
e
= 4.3 - 46 A
Motor: 0.75 - 11 kW (230 V, 50 Hz), 1 - 15 HP (230 V, 60 Hz)
Figure 16:DA1-32…FB-…
I
e
= 61 - 248 A
Motor
230 V (U
LN
= 3 ~ 230 V)
L1
L2
L3
PE
U
V
EMC Filter
W
L1/L
L2/N
L3
BRDC+
Brake Chopper
M
3 ∼
I
e
FS2, FS3, FS4