2 Engineering
2.3 Safety and switching
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 43
2.3.3 Cable cross-sections
The mains cables and motor cables must be sized as required by local
standards and by the load currents that will be involved.
The PE conductor’s cross-sectional area must be the same as the phase
conductors’ cross-sectional area. The connection terminals marked with
must be connected to the earth-current circuit.
If there are leakage currents greater than 3.5 mA, a reinforced earthing (PE)
must be connected, as required by standard EN 61800-5-1. The cable cross-
section must be at least 10 mm
2
, or the earthing system must consist of two
separately connected earthing cables.
A symmetrical, fully screened (360°), low-impedance motor cable must be
used. The length of the motor cable depends on the RFI class and the
environment.
For US installations, UL-listed fuses, fuse bases, and cables (AWG) should be
used exclusively. These cables must have a temperature rating of 70 °C
(158 °F), and will often require installation inside a metal conduit (please
consult the applicable local standards).
NOTICE
The specified minimum PE conductor cross-sections
(EN 61800-5-1) must be maintained.
Section 6.2, „Specic rated operational data“, page 147
provides the leakage currents for the individual models.
Section 3.5, „EMC installation“, page 83 goes over the EMC
requirements for the motor cables.
For the rated cable cross-sectional areas for DA1 variable
frequency drives, please refer to the technical data chapter in
Section 6.4, „Cable cross-sections“, page 161.