6 Technical Data
6.8 Radio interference suppression filter
170 DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Table 42: Assigned radio interference suppression filter (single-phase)
Device Type
Size Input
current
Radio interference suppression filter, single-phase
Max. mains voltage U
LN
: 250 V +0%, 50/60 Hz ±10%
Max. ambient temperature: 50
o
C
Part no. rated
operational
current
Leakage
current
(IEC38, ±10 %)
Maximum motor cable length
based on RFI class
C1 C2 C3
I
LN
I
e
I
PE
l l l
A A mA m A m A m A
Mains voltage 115 V
Supply voltage (50/60 Hz) U
LN
110 (-10 %) - 115 (+10 %) V
U
e
115 V AC, single-phase / U
2
230 V AC, three-phase (internal voltage doubler)
DC1-1D2D3NN-A20CE1 FS1 7.8 DX-EMC12-014-FS1 14 8 25 75 100
DC1-1D4D3NN-A20CE1 FS1 15.8 DX-EMC12-019-FS1 19 8 25 75 100
DC1-1D5D8NB-A20CE1
FS2 21.9 DX-EMC12-025-FS2 25 8 25 75 100
Mains voltage 230 V
Supply voltage (50/60 Hz) U
LN
200 (-10 %) - 240 (+10 %) V
U
e
230 V AC, single-phase / U
2
230 V AC, three-phase
DC1-122D3NN-A20CE1 FS1 3.7 DX-EMC12-014-FS1 14 8 25 75 100
DC1-124D3NN-A20CE1 FS1 7.5 DX-EMC12-014-FS1 14 8 25 75 100
DC1-127D0NN-A20CE1
FS1 12.9 DX-EMC12-014-FS1 14 8 25 75 100
DC1-127D0NB-A20CE1 FS2 12.9 DX-EMC12-014-FS2 14 8 25 75 100
DC1-12011NB-A20CE1 FS2 19.2 DX-EMC12-025-FS2 25 8 25 75 100
DC1-12015NB-A20CE1 FS3 29.2 DX-EMC12-031-FS3 31 8 25 75 100