2.10 Switching to the output side
54 DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Figure 19: Example: Parallel connection of several motors to one variable frequency drive
When using vector mode (P-60 = 0), two motors with identical
output classes can be connected (e.g., calendar drive).
When using vector mode with P-60 = 2, 3 or 4, it is not
permissible to run multiple motors connected in parallel!
a Motor choke (DX-LM3…) or sine filter
(DX-SIN3…)
Q11, Q12, Q13, …: Motor protection
(utilization category AC-3)
F1, F2, F3, …: Overload relay (bimetallic
relay or PKE)
Q11
F1
M1
Q12
F2
M2
Q13
F3
M3
U1 V1 W1 U1 V1 W1 U1 V1 W1
M
3
˜
M
3
˜
M
3
˜